YOUR ELECTRICITY · INSIDE THE CONSUMER UNIT

How an MCB works.
See what makes it trip.

A miniature circuit-breaker, or MCB, opens a circuit when too much current flows. A sustained overload heats its thermal strip. A sufficiently large fault current operates its magnetic release rapidly.

Switch example appliances on below, watch the load rise, then look inside the breaker as it opens.

WATCH THE MCB LESSON · 5:41

Look inside. Follow the current. See it trip.

Watch the narrated lesson using this 3D MCB, then try the appliance loads in the interactive demonstration below.

Press Play to start. English (United Kingdom) captions and full screen are available in the player.

Jump to a chapter
  1. 0:00 Inside a miniature circuit-breaker
  2. 0:34 Follow the current path
  3. 1:11 Choose a rating and build a load
  4. 1:51 A sustained overload heats the strip
  5. 2:31 A short circuit triggers magnetic release
  6. 3:03 How the arc dies away
  7. 3:37 Resetting does not remove the cause
  8. 4:12 The circuit outside the breaker
  9. 4:49 Keep the covers on. Keep learning.
Read the complete film transcript

Inside a miniature circuit-breaker

When a miniature circuit-breaker, or M C B, trips, the handle only shows us the result. Inside, a small movement releases a mechanism that opens the contacts. Two triggers can start it: heat from a sustained overload, or magnetism from a sufficiently large fault current. In this cutaway, we can follow both, right down to the moving pin, bending strip and dying arc. The cover is removed for explanation; keep protective covers fitted on real equipment.

Follow the current path

Switch on the example and watch the handle close gradually. With the contacts touching, current passes through the connected conductors, contacts, braids, coil winding and thermal strip. The winding carries the load current and creates a magnetic field. Normal current does not pass through the iron pin or surrounding yoke. Red identifies conducting parts: deeper red means more amps, not higher temperature. The highlight helps us follow the route; it does not reproduce the frequency of alternating current.

Choose a rating and build a load

The interactive page offers B six, B sixteen, B thirty and B forty examples. The number is the rated current, not an exact trip threshold. These are comparisons, not guidance for choosing protection. Add appliances to compare demand. The gas boiler's one hundred and twenty watts powers its pump, fan and controls, not its gas heating. The immersion cylinder has two independent three-kilowatt elements. Try the electric hob and microwave too. The microwave figure is electrical input, not cooking output.

A sustained overload heats the strip

Here is the B forty with the boiler, both immersion elements, kettle, toaster and electric heater selected. Together they demand twelve thousand, three hundred and twenty watts. At our assumed two hundred and thirty volts, that is about fifty-three point six amps. Watch the thermal strip warm and bend until it releases the mechanism. The contacts open quickly, and the current reading falls to zero. The magnetic pin stays at rest. Heating is accelerated here; the demonstration's running time does not predict a real breaker's trip time.

A short circuit triggers magnetic release

A short circuit can create a low-impedance path that bypasses the intended load. If the current is sufficiently high, the coil operates the magnetic pin and releases the mechanism rapidly. It does not wait for the thermal strip to heat. Compare that pin movement with the thermal trip. This example assumes a large fault current. Real fault current depends on the supply and fault path, not simply the appliance wattage.

How the arc dies away

Opening contacts under load can produce an electrical arc. Runners guide it towards electrically separate metal plates, which divide and cool it until it dies away. These plates are not the ordinary load-current path. We have slowed the interruption to make it visible. The zero-amp reading describes the circuit after the trip; the bright arc illustrates the interruption that just happened. It is not continuing appliance current. Watch it split, fade and disappear.

Resetting does not remove the cause

After a thermal trip, warmth remains even though current has stopped. The strip moves back as it cools. If the overload returns while the breaker is warm, it may trip sooner. Some mechanisms need the handle moved fully off before resetting. A persistent fault is different: closing the contacts restores fault current and causes another trip. The breaker is not testing disconnected wiring first. Resetting the handle removes neither a fault nor an overload.

The circuit outside the breaker

Outside the breaker, a ring final circuit gives current two routes to each socket. Its two line ends return to the same breaker; neutral and protective conductors return to their appropriate bars. Loads connect in parallel. Current divides according to the paths and load positions, not automatically half each way. The breaker sees the total supplied current. A broken ring may still power sockets while part of its cable is overloaded. An M C B does not test ring continuity.

Keep the covers on. Keep learning.

At home, note which device tripped and what was running. Keep covers fitted. Do not touch or reset wet, damaged, unusually hot or scorched equipment, or anything with a burning smell. Do not keep resetting. If the circuit trips again, will not stay on, or you are unsure, leave it off and contact a qualified electrician. Now try the interactive animation on the E P H G website. Rotate the model, choose appliances and watch the response. The lesson link is in the description. Subscribe, and let us know in the comments if you would like more videos like this. We are working towards central heating and hot water boilers.

01 / TRY THE DEMONSTRATION

Build a load.
Watch the response.

Choose an MCB example, switch on the supply, then add loads. Drag the model to look around it.

B6 · 0.0 AOFF

Loading the cutaway…

0 A: normal0–70 A+: pale to deep red

Red marks current-carrying components; deeper red means more amps. One scale applies to every rating.

Follow the current path

Incoming terminal → contacts → braid → coil → braid → bimetal strip → outgoing terminal. Red marks this path, not every metal part. The moving highlight traces the route; it does not simulate AC frequency. Red is an illustration, not real metal colour, temperature or voltage. At 70 A and above the scale saturates. No colour is not proof of safe isolation. See the teardown at 3:36.

When contacts open under load, an arc can form. Runners guide it towards the electrically separate metal plates, which split and cool it. Normal appliance current does not flow through the plate bank. See the arc-control parts from 8:10.

The circuit is switched off.

Choose some example loads, then select Switch ON. No current flows while the contacts are open.

Choose an example while the breaker is OFF.

Current flowing0.0 A
Selected load0 W0.0 A when supplied
0%
0%

No current flowing.

Cool

Warmth and bend towards the illustrated release. Timing is accelerated and illustrative, not a real trip-time prediction.

Choose some example loads, then select Switch ON.

Switch example appliances on or off

Illustrative electrical loads at 230 V. The microwave value is electrical input, not cooking output. Appliance ratings and cycling vary. These examples are not a design for one real circuit.

Ready

Illustrative timing. Heating and movement are accelerated. Sustained overloads, including B40 at 53.6 A, demonstrate a possible thermal trip. The arc plays automatically in your current view, then dies away. Its timing is slowed for visibility; the current reading shows the interrupted circuit at zero. Real trip times depend on the device and conditions; this is not a trip-time calculator or a test of a real installation. The strip indicator represents relative warmth and bend, not degrees Celsius. A higher-rated MCB is not a remedy for an overloaded circuit.

Try this: select B40 with the gas boiler, both immersion elements, kettle, toaster and electric heater for 12,320 W (53.6 A). Switch ON and watch the strip warm, bend and release the mechanism, and watch the arc die away in the same view. Try B6 with a kettle, or compare the separate short-circuit switch. After a trip, move OFF/reset and let the strip cool before trying again. Selected appliances remain selected when the breaker opens, but current flowing falls to zero.

02 / TWO DIFFERENT RESPONSES

An overload builds heat.
A short circuit can act much faster.

THERMAL RELEASE

Too much current for too long

An overload uses the intended current path through the appliances, but draws more current than the circuit can safely carry. The MCB’s bimetal strip heats and bends. When it releases the mechanism, the contacts open.

A larger overload generally produces a shorter delay. A breaker that is already warm can respond differently from a cold one.

MAGNETIC RELEASE

A large fault current

A short circuit can create a low-impedance path that bypasses the intended load. If the resulting current reaches the magnetic operating range, the coil moves its armature or pin and releases the mechanism rapidly.

The contact opening and arc-control parts then interrupt the current. A real fault current depends on the supply and fault path, not simply the appliance wattage.

The rating is not an exact trip threshold. A B16 does not necessarily open the instant current reaches 16.01 A. The number is its rated current; the letter identifies its trip characteristic. Actual operation follows the particular device’s time–current curve and reference conditions.

For example, Schneider Electric explains thermal test currents, reference temperature and conventional times. Those test conditions do not calibrate this demonstration or the legacy breaker shown in the cutaway.

Type B examples: rating and magnetic operating band
MarkingRated current3–5 times rated current
B66 A18–30 A
B1616 A48–80 A
B3030 A90–150 A
B4040 A120–200 A

The Type B magnetic band is given in Crabtree’s Polestar technical data. It is a conventional operating band, not an acceptable continuous load or a guarantee of an identical pickup point. The historical document does not calibrate this model’s old breaker or its illustrative intermediate variants.

03 / THE PARTS WORK TOGETHER

What is inside an MCB?

Both sensing elements release the contact mechanism. The handle, springs, contacts and arc-control parts each have a different job.

01

Terminals and conductors

These connect the supply and circuit to the internal current path. The permitted supply connection and physical layout depend on the product.

02

Fixed and moving contacts

Touching contacts complete the circuit. Separating them starts the interruption of current; arc control is also needed when an arc forms.

03

Bimetal strip

Two bonded metals expand differently as they warm. The resulting bend operates the thermal release during a sustained overload.

04

Magnetic coil and pin

The coil is in series with the load: the same load current passes through its enamel-insulated winding and makes a magnetic field. A sufficiently large fault current actuates the pin. Normal load current passes through the winding, not the iron pin or surrounding yoke.

05

Handle, latch and springs

The handle sets the mechanism; stored spring energy helps the contacts move quickly. A trip-free mechanism can open even if the handle is held ON. Never restrain a real breaker.

06

Arc runners and splitter plates

When contacts open under load, an arc can form. Runners guide it into the chute, where electrically separate metal plates divide and cool it. Normal load current does not jump between these plates; their arc-control role begins during interruption.

07

Insulating case

The moulded case supports and separates the parts. The cutaway removes it only for explanation. Keep a real device closed; it is not a household repair item.

Follow the current path in John Ward’s teardown, 4:15–5:27. ABB’s miniature circuit-breaker application guide, PDF pages 6–7 (printed 2–3), explains the separate thermal, magnetic and arc-control parts. These references explain the principles; they do not calibrate this Crabtree model’s timing or illustrative hidden dimensions.

04 / THE CIRCUIT IT PROTECTS

A ring final circuit gives current
two routes to each socket.

Often called a “ring main”, a ring final circuit returns to its starting point in the consumer unit. In this single-pole MCB example, both line ends connect to the same breaker, the neutral ends to the appropriate neutral bar, and the protective-conductor ends to the earth bar.

A representative ring final circuit: two routes to each socket The brown line ring leaves and returns to the same MCB, the blue neutral ring to the same neutral bar, and the green and yellow protective conductor ring to the earth bar. Three sockets connect in parallel to line and neutral. The middle socket supplies an illustrative load. Bridges show crossings without electrical connections; solid dots show connections. The drawing is explanatory, not an installation design. A ring final circuit Three separate conductor rings. Two paths connect each socket to the consumer unit. CONSUMER UNIT Socket 1 Socket 2 Socket 3 MCB · line only Neutral bar Earth / CPC bar LLL NNN CPCCPCCPC Load Each ring returns to its own starting terminal or bar. Dots = joined. Bridges = crossing only. CPC is not the normal load-current return. Explanatory layout only. AC current reverses; any movement is deliberately slowed.
A representative ring final circuit, separate from the appliance demonstration above. It is an explanatory drawing, not an installation design.

Loads connect in parallel

Current can divide between the two line routes and return by the neutral routes. The split depends on path impedances and load positions; it is not automatically half each way. The MCB sees the total supplied current.

The green/yellow protective conductor is not the intended normal load-current return. Neutral is not safe to touch.

A broken ring may still work

A discontinuity can leave sockets operating through the remaining route. Part of the cable may be overloaded without the total current tripping the MCB. The breaker does not test ring continuity or detect every loose connection.

Many socket circuits are radials. Ratings, cables and protection must be selected and verified for the actual installation.

Read the IET’s discussion of ring final circuits and their failure risks, and its explanation of protective-conductor currents.

05 / AFTER A TRIP

Resetting the handle
does not remove the cause.

It trips again immediately

If a fault remains, closing the contacts restores the fault current and the breaker can trip again too quickly to see. It is responding after current resumes, not testing disconnected wiring before you switch on.

It stays on, then trips later

A sustained overload may take time to heat the strip. If the load returns, heating resumes. Existing warmth, ambient temperature and neighbouring devices can affect the response.

The handle will not stay on

Some devices must first move fully OFF to reset. Follow the installed product’s instructions. A hot element, an immediate retrip or a damaged mechanism can look similar; do not force it.

In the demonstration, clear the short-circuit switch or remove the excess load, move the handle OFF/reset, then switch ON. A real installation may still have a fault even if it stays on again.

A REAL TRIP AT HOME

Keep the covers on.
Know when to stop.

Note which device moved, what lost power and what was running. Use only normal accessible controls. If it is safe, switch off and unplug a suspect portable appliance; do not reconnect it to recreate the fault.

Do not keep resetting. Follow the installed device’s instructions. If it will not stay on, trips again, or you are unsure, leave the affected circuit off and contact a qualified electrician.

See Electrical Safety First’s electrical safety guidance.

DIFFERENT DEVICES, DIFFERENT JOBS

MCB, RCD or RCBO?

MCB

Responds to overcurrent: overloads and sufficiently high fault currents. It is primarily part of the protection for the circuit wiring.

RCD

Responds to an imbalance between the monitored line and neutral currents. Small leakage currents can operate an RCD without operating an MCB.

RCBO

Combines residual-current and overcurrent protection. A trip may have more than one possible cause.

Compare the devices in a consumer unit →

About this lesson

Prepared by Martin Smith for EPHG Limited, drawing on practical experience.

This EPHG lesson combines a reference-led 3D cutaway with a simplified load demonstration. Movement and heating are accelerated for viewing. The hidden linkage, coil and strip variants are not measured manufacturer replicas; B16 and B30 geometry is illustrative. A selected rating changes the example, not the suitability of any real circuit.

Example appliance powers are stated in the controls. Current is estimated as electrical watts ÷ 230 V; power factor, starting currents, duty cycles, plug-fuse coordination and real supply impedance are not modelled. The short-circuit scenario assumes 1,000 A when the contacts close; it is not calculated from a real installation. The simulator cannot certify cable sizing, protection selection or fault diagnosis.

Updated , with AI-assisted research and production. No review by a named qualified electrician is claimed. The written explanation remains available without the interactive model.